Individual pricing for large scale projects and wholesale demands is available.
Mobile/WhatsApp/Wechat: +86 156 0637 1958
Email: info@evlithium.com
Flexible
All-in-one design and highly integrated
Modular design with different optional parts
NEMA 3R / IP54 rated
Parallel installation side-by-side or back-to-back
Compatible
Compatible with different module series,150~750Vdc
Grid-tied and Off-grid
480Vac 3P4W & 240Vac 2P
Optional PV input
Optional backup module
DC Side |
|
Charging and Discharging voltage range |
150V-750V(350V-750V @full load) |
Rated Power |
30kW*n(1~3) |
Maximum Charging and Discharging Current |
90A*n(1~3) |
DC Bus Side (Optional) |
|
PV Voltage Range |
250V-830V |
Maximum Input Current |
65A*n(1~3) |
AC Side |
|
Rated Output Power |
30kVA*n(1~3) |
Maximum Apparent Power |
33kVA*n(1~3) |
Maximum Active Power |
30kW*n(1~3) |
AC Voltage Grid-tied |
400V(- 15%~15%) 3P4W+PE /480V(- 15%~15%) 3P3W+PE |
AC Voltage Off-grid |
400V(-20%~20%) 3P3W+PE /480V(-5%~5%) 3P3W+PE |
AC Frequency |
50Hz/60Hz(-2.5Hz~2.5Hz) |
THDi |
<3% |
General Specification |
|
Dimension(W*H*D) |
2100*2450*1300mm |
Cooling |
Forced air cooling for power electronics 5kW Air-conditioned for battery system (pre- installed) |
Enclosure |
NEMA 3R/IP54 |
Weight |
3800kg |
Operation Altitude |
3000m(>2000m derating) |
Operation Temperature |
-20¡æ~55¡æ(De- rating over 45°C) |
Operation Humidity |
0-95%(No condensing) |
Noise |
70 dB |
Power Converter Compatibility |
|
Model |
PWS2-30M- EX PWS2-30P- EX/NA |
Max PCS units |
3 |
AC power range |
30kW (400 or 480Vac & 350-750Vdc)*n units (n=1,2,3) 15kW (400 or 480Vac & 150-350Vdc)*n units (n=1,2,3) |
DCDC Charger Compatibility |
|
Model |
PDS1-45K |
Max DCDC units |
3 |
PV Input Power |
45kW *n units (n=1,2,3) |
PV Input Voltage Range |
200V-810V |
Battery Compatibility |
|
Manufacture |
CATL |
Cell Type/Module Energy |
LFP 100Ah/10.24kWh(2P16S) |
Battery Configuration |
2P16S*13S*2P |
Nominal Energy |
266.24kWh |
Nominal Voltage |
665.6V |
Voltage Range |
582.4V~748.8V |
Auto-switching Compatibility |
|
Model |
PWD- 100K |
Switching Time |
Active Switching: Seamless Passive Switching: 30ms |
Communication |
|
Communication Port |
CAN/RS485/Ethernet |
Communication Protocol |
Modbus TCP/RTU,IEC104 |
BMS Access |
Support |
Optional Components |
|
Fire Fighting System |
Sensor tube, with the agent of NOVEC 1230 or FM200 or water |
Built- in transformer |
400V/400Vac or 480V/480Vac, 100kVA |
Built- in gateway |
For Peak-shaving, demand charge management or back- up power supply. |
Aux power |
220V single phase built- in, up to 5kw transformer 120V built- in, up to 3kW |
Salt spray prevention |
Optional Salt spray prevention version with special coating and filter |
Compliance |
UL9540 |
Appearance
90KW/266KWH All-in-one Outdoor cabinet ess.pdf