Liquid Cooling Commerical Energy Storage System Solutions Grid-connected
(535kWh/250kW, 570kWh/250kW, 1070kWh/250kW, 1145kWh/250kW)
LOW COSTS
SAFE AND RELIABLE
EFFICIENT AND FLEXIBLE
SMART AND ROBUST
Product Name |
ST535kWh-250kW-2h |
ST570kWh-250kW-2h |
ST1070kWh-250kW-4h |
ST1145kWh-250kW-4h |
Battery cabinet data |
||||
Cell type |
LFP |
|||
System battery configuration |
300S2P |
320S2P |
300S2P*2 |
320S2P*2 |
Battery capacity (BOL) at DC side |
537kWh |
573kWh |
537kWh*2 |
573kWh*2 |
System output voltage range |
810~1095V |
864~1168V |
810~1095V |
864~1168V |
Dimensions of battery unit (W * H * D) |
2180*2450*1730mm (single cabinet ) |
|||
Weight of battery unit |
5900kg (single cabinet) |
6100kg (single cabinet) |
5900kg (single cabinet) |
6100kg (single cabinet) |
Degree of protection |
IP54 |
|||
Anti-corrosion grade |
C3 |
|||
Relative humidity |
0 ~ 95 % (non-condensing) |
|||
Operating temperature range |
-30 to 50¡ãC (> 45¡ãC derating) |
|||
Max. working altitude |
3000m |
|||
Cooling concept of battery chamber |
Liquid cooling |
|||
Fire safety equipment |
Aerosol ,flammable gas detector and exhausting system |
|||
Communication interfaces |
Ethernet |
|||
Communication protocols |
Modbus TCP |
|||
Compliance |
IEC62619,IEC63056,IEC62040,IEC62477,UN38.3 |
|||
PCS cabinet data |
||||
Nominal AC power |
250kVA@45¡ãC |
|||
Max. THD of current |
<3% (at nominal power) |
|||
DC component |
<0.5% (at nominal power) |
|||
Nominal grid voltage |
400V |
|||
Nominal grid voltage range |
360V~440V |
|||
Nominal grid frequency |
50/60Hz |
|||
Nominal grid frequency range |
45Hz~55Hz, 55-65Hz |
|||
Dimensions (W*H*D) |
1800*2450*1230mm |
|||
Weight |
1600kg |
|||
Degree of protection |
IP54 |
|||
Anti-corrosion grade |
C3 |
|||
Allowable relative humidity range |
0 ~ 95 % (non-condensing) |
|||
Operating temperature range |
-30 to 50¡ãC (> 45¡ãC derating) |
|||
Max. working altitude |
3000m |
|||
Communication interfaces |
Ethernet |
|||
Communication protocols |
Modbus TCP |
|||
Compliance |
IEC61000, IEC62477, AS4777.2 |