The 3kw Hybrid Solar Power Inverter with nominal AC output power 3kW can work with a battery bank as backup power to make the best use of time-of-use policy or to keep a continuous power supply in case of grid outage or poor wind turbine/diesel generator performance, which may help end users maximize self-consumption and enhance energy independence.
Specifications
Item
Parameters
Battery Parameters
Compatible Battery Type
Lithium-ion,
Lead-acid
Nominal Battery Voltage
48V/51.2V
Battery Voltage Range
40V¡«60V
Capacity of Battery
2¡«20KWh
Maximum Charging/Discharging Current
66A/66A
Maximum Charging/Discharging Power
3600W/3600W
Max. Charging Voltage
59V
Charging Curve (Lithium-ion)
3stages
Charging Curve (Lead-acid)
3stages
Depth of Discharge (Lithium-ion/Lead-acid)
80%/50%
Input DC (PV Side)
Max. DC Input Power
6600W
Max. DC Input Power for Single MPPT
4000W
DC Input Voltage Range
100V¡«550V
Nominal DC Input Voltage
360V
MPPT Operating Voltage Range
100V¡«500V
Full Power MPPT Voltage Range
140V~440
Start-up Voltage (On-grid mode)
120V
Max. DC Input Current
13A/13A
Max. DC Input Short Current
13.7A/13.7A
MPPT Number/ (Strings per MPPT)
2(1+1)
Output AC(Grid)
Nominal Output Power
3000W
Max. Output Power
3000VA
Nominal AC Voltage
230V
Operation Phase
Single Phase
Max. Input/Output Current
15A
Nominal AC Frequency
50Hz/60Hz
THDI
<3%
Power Factor
>0.99@rated power -0.8¡«+0.8 adjustable
UPS Output - with Battery
UPS Max. Output Power without Solar
3000W
UPS Max. Output Power with Solar
3000W
UPS Nominal Output Voltage
230V
UPS Nominal Output Frequency
50Hz/60Hz
UPS Nominal Output Current
13A
Peak Power
4500W,30s
THDV
<3%@R-load
Switching Time
10ms
Efficiency
MPPT Efficiency
99.90%
Max. Efficiency
97.90%
EU Efficiency
97.50%
Battery Charging Efficiency
94.50%
Battery Discharging Efficiency
94.50%
Protection
Reverse Polarity Protection
YES
Anti-islanding Protection
YES
AC Short-circuit Protection
YES
Leakage Current Protection
YES
Grid Monitoring
YES
DC Switch
YES
Ingress Protect Degree
IP65/NEMA4X
PV Insulation Detection
YES
Ground Fault Monitoring
YES
Over Current Protection
YES
Over Voltage Protection
YES
Battery Soft Start Protection
YES
SPD Protection
YES
General Data
Dimension(mm)
455W*476 (565) H*181D
Weight
20kg
Display
Color LCD+LED
Topology
Transformerless (Solar), HF(Battery)
Ambient Temperature Range
-25¡«60¡æ
Standby Losses
<5W
Cooling
Natural Convection
Relative Humidity Range
0¡«100%
Max. Operating Altitude
2000m
Noise
<25dB
Communication
RS485, Wi-Fi, CAN
Warranty
5 Years
Standard & Certification
EMC
EN61000-6-1, EN61000-6-2, EN61000-6-3
Safety Standard
IEC62109-1,
IEC62109-2, IEC62040
Grid Standards
Features
An energy storage system can support both single phase and three phase parallel configuration with a maximum of 10 units of HYH-3K-Pro inverters for either hybrid or AC-coupled applications.